Hi Viewers I am Afreen Ali . i bring this video for basic chilled
water pump head for primary pump / head
for secondary pump. Kindly Subscribe my channel AfreenAli
Head for primary pump / head for secondary pump
Head for primary pump = chiller friction losses + pipe
losses for longest pass + fitting losses
Head for secondary pump = pipe losses for longest pass +
fitting losses + last equipment in the longest pass ( FCU or AHU )
there is tow way to calculate the pump head
1- equivalent length method and you may found it in
carrier handbook.
2- k factor you will find it in ASHRAE.
the main concept for calculation and sizing
pipe size < = 2" -----> Max velocity = 4 fps
pipe size > 2" --------> max friction losses
4ft wg / 100 ft
there are many programs for pump head calculation like
H-sym (Elite) , Trane pipes , pipe flow expert
Example mention below with details
There is a difference between the pressure required from
pump which is generated by the pump itself (dP)and the hydrostatic pressure
generated by elevation
the fist one, we considered it for moving the fluid but
the second one we considered it for determining the max. working pressure
inflicted upon pipes, pump's parts (casing , mechanical seal ,....)and all the
elements in network
example:
If we calculate dP=5bar required from pump to move the
water with the required flow rate.
these 5bar may be from 1bar to 6bar
and may be from 15bar to 20bar
The 2 cases have the same dP (friction losses and
fittings ,....) but not the same max. working pressure
Such as (Example), the maximum pressure the chiller would
see, if on the bottom floor, is approximately 900 ft (due to elevation) + 140
ft (due to pump shut off pressure, which is basically the TDH provided by the
pump during operation and the shut off pressure of the pump) for a total static
pressure of 1040 ft (450 psi) per Solution A. This would exceed the rated
pressure of the described fitting/chiller.
If the chiller is on the top floor (Solution C), then the
total pressure the chiller would see would be 65 psi. This would be within the
pressure rating of the fitting/chiller. The pump is still contributing 140 ft
to the pressure, but because of the difference in elevation, the static effect
is much less.
In this case you would specify fittings/pipe with higher
pressure ratings on the lower floors and decreasing ratings as you went up. You
would locate the chiller at a level where the pressure does not exceed its
maximum pressure.
I hope that helps.
Kindly Subscribe my channel AfreenAli
No comments:
Post a Comment